TECHNICAL SPECIFICATIONS

 

ModelMUCHR-28-H6AMUCHR-40-H6AMUCHR-45-H6AMUCHR-56-H6A
CodeCL23907CL23909CL23910CL23911
Cooling (1)CapacitykW27,539,3244,2354,4
kcal/h23.65333.82038.04346.790
ConsumptionkW7,021213,6817,91
EERkW/kW3,923,283,233,04
Heating (2)CapacitykW28,2440,6345,1557,48
kcal/h24.29034.94638.83449.439
ConsumptionkW6,7412,0813,5718,69
COPkW/kW4,193,363,333,08
Indoor unitModel MVD-280T1/DHN1-BD400T1/N1-FD450T1/N1-FD560T1/N1
CodeCL23383CL23187CL23188CL23186
Power supplyF, V, Hz1N-, 220-240V, 50Hz
Rated CurrentA612,512,515,5
Air flow (H / M / L)m3/h4820 / 4660 / 46207474 / 6072 / 49957474 / 6072 / 49959550 / 7950 / 6600
Static pressure avail. (ESP)Pa62 (40 – 200)200 (50 – 280)200 (50 – 280)200 (50 – 280)
Sound pressure (H/M/L) (3)dB(A)57 / 53 / 5061 / 59 / 5661 / 59 / 5663 / 60 / 57
Dimensions (W x H x D)mm1450 x 505 x 9251970 x 668 x 902,51970 x 668 x 902,51970 x 668 x 902,5
Weightkg108232232232
Drain connectionmm32323232
Power cable (5)mm22 x 2,5 + T2 x 4 + T2 x 4 + T2 x 4 + T
Outdoor UnitModel MVD-V5X280W/V2GN1V5X400W/V2GN1V5X450W/V2GN1V5X560W/V2GN1
CodeCL23301CL23303CL23304CL23306
Power supplyF, V, Hz3N-, 400V, 50Hz
Rated CurrentA2127,329,941,2
Air flow (H)m3/h12.00014.00014.00016.000
Static pressure avail. (ESP)Pa20 (0 - 40)20 (0 - 40)20 (0 - 40)20 (0 - 40)
Sound pressure (4)dB(A)59626263
Dimensions (W x H x D)mm990 x 1635 x 7901340 x 1635 x 7901340 x 1635 x 7901340 x 1635 x 790
WeightKg219315315340
Power cable (5)mm24 x 6 + T4 x 6 + T4 x 10 + T4 x 16 + T
RefrigeranteTypeR410A
Preloaded amountkg9131316
Additional load (from 0 m)kg/m0,0570,110,110,17
Pipe connectionsLiquid Linemm (")9,52 (3/8")12,7 (1/2")12,7 (1/2")15,9 (5/8")
Gas Linemm (")22,2 (7/8")28,6 (1 1/8")28,6 (1 1/8")28,6 (1 1/8")
Pipes distances (6)Max. Verticalm110
Totalm175
Communication cablemm23 x 0,75 (Shielded)
Wired controllerModelKJR-29B
TypeWired
Temp. range performanceCoolingºC-5 to 43
HeatingºC-20 to 24

Notes:

(1) Nominal cooling conditions: Indoor 27 °C DB, 19 °C WB and outdoor 35 °C DB, pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7 °C DB, pipe length of 8 m and a height difference of 0 m.

(3) Noise level measured in semi-anechoic chamber at 1m front distance and 1.4 m height.

(4) Noise level measured in semi-anechoic chamber at 1m front distance and 1.3 m height.

(5) Power wiring recommended for L < 20 m, for longer distances it should be calculated.

(6) Pipe length when the outdoor unit is lower installed than indoor units. Otherwise, see part MVD.

The above design and specifications are subject to change of product improvement without prior notice.