MUCR-H3 Series

Commercial range

Split tipo conducto serie MUCR-H3

Split duct type MUCR-H3 Series

Characteristics

  • Refrigeration extreme conditions
  • Heating control 8°C
  • Two environment sensor
  • 3 night modes
  • Smart zone controller *
  • Timer function
  • Turbo operation
  • Memory/self-restart function
  • Temperature of low dehumidification
  • Fan with 7 speeds
  • Hotel card system *
  • 2 controllers for 1 unity *
  • Standby 1W
  • Problems solution
  • Regulation PFC high digital efficiency
  • Sinusoidal technology 180°C

* Optional

     Technical Documentation

Data SheetESENFR
Owner's and installation manualESENFRDE
Technical manualEN

TECHNICAL SPECIFICATIONS

 

ModelMUCR-12-H3MUCR-18-H3MUCR-24-H3MUCR-30-H3MUCR-36-H3MUCR-42-H3MUCR-48-H3MUCR-60-H3
CodeCL 20 862CL 20 863CL 20 864CL 20 865CL 20 866CL 20 867CL 20 868CL 20 869
Cooling capacitykW3,5578,31011,51416
Heating capacitykW3,85,689,21213,515,516,5
Pdesignh (-10ºC)kW34,577,610,410,511,812,5
SEER/SCOPW/W5.6/4.05.1/3.85.1/3.85.1/3.85.1/3.85.1/3.85.1/3.85.1/3.8
SupplyV-Hz-F230-50-1230-50-1230-50-1230-50-1230-50-1230-50-1230-50-1400-50-3
Indoor unit
Air flow ratem3/h7501.0001.4001.4002.1002.1002.4003.000
Static pressureStandard (Pa)2525253737375050
Range (Pa)0~300~300~1000~1000~1500~1500~1500~150
Sound pressure leveldB(A)37/36/34/2840/39/36/2847/46/44/4047/46/44/4053/52/48/4453/52/48/4455/53/49/4556/55/51/46
Dimensions (W x H x D)mm1.037x266x7211.037x266x7211.239x268x5581.239x268x5581.226x290x7751.226x290x7751.340x350x7501.340x350x750
Net weightkg3333343446465656
Outdoor unit
Air flow ratem3/h3.2003.2004.0004.0005.1006.6006.6006.600
Sound pressure leveldB(A)5556575863626263
Dimensions (W x H x D)mm848x540x320955x700x396980x790x427980x790x4271.107x1.100x440958x1.349x412958x1.349x4121.085x1.365x427
Net weightkg344767719295105124
Cooling pipes (inches)Liquid1/4"1/4"3/8"3/8"3/8"3/8"3/8"3/8"
Gas3/8"1/2"5/8"5/8"5/8"5/8"5/8"3/4"
Refrigerant chargekg1,21,42,22,43,53,745

Warning:
1. Design and specifications are subject to change without prior notice of product improvement.
2. The values of noise level match with values obtained in the anechoic chamber.

PRE-INSTALLATION REQUIREMENTS

 

MODELPIPESELECTRICAL CONNECTIONS
GasLiquidMax. Length (B)Max. slope (A)Preloading untilAdditional chargeSupplyCom. (C/F)
Indoor (E)Outdoor (D)
MUCR-12-H33/8"1/4"20 m15 m7.5 m30 gr/m2 x 1.5 + T2 x 2.5 + T2 x 0.75
MUCR-18-H31/2"1/4"20 m15 m7.5 m30 gr/m2 x 1.5 + T2 x 2.5 + T2 x 0.75
MUCR-24-H35/8"3/8"30 m15 m7.5 m60 gr/m2 x 1.5 + T2 x 2.5 + T2 x 0.75
MUCR-30-H35/8"3/8"30 m15 m7.5 m60 gr/m2 x 1.5 + T2 x 2.5 + T2 x 0.75
MUCR-36-H35/8"3/8"50 m30 m7.5 m60 gr/m2 x 1.5 + T2 x 2.5 + T2 x 0.75
MUCR-42-H35/8"3/8"50 m30 m7.5 m60 gr/m2 x 1.5 + T2 x 2.5 + T2 x 0.75
MUCR-48-H35/8"3/8"50 m30 m9.5 m60 gr/m2 x 1.5 + T2 x 6 + T2 x 0.75
MUCR-60-H33/4"3/8"50 m30 m9.5 m60 gr/m2 x 1.5 + T3 x 2.5 + T2 x 0.75

Tuberias MUCR-H3Conexiones MUCR-H3