MUC-W7 Series

Industrial range

MUC-W7

Universal Fan Coil unit – Horizontal / vertical MUC-W7 series

Characteristics

  • Universal 2 pipes Fan Coil Unit
  • Floor or ceiling installation (vertical / horizontal)
  • Low noise and low-energy consumption DC fan motor
  • Front air inlet (Version CE)
  • Without the need of using supporting feet (Version CE)
  • Includes condensate collecting tray in L-form for the valve

     Technical documentation

Data SheetES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Owner's and installation manualES 18X18EN 18X18
Service manualEN 18X18

TECHNICAL SPECIFICATIONS

 

MUC-W7/SE-CE Model711161924
CodeWithout casing (Version SE)CL04580CL04581CL04582CL04583CL04584
With casing (Version CE)CL04590CL04591CL04592CL04593CL04594
CoolingCapacity (High / Medium / Low) (*1)kW2,07 / 1,52 / 1,073,25 / 2,63 / 2,124,57 / 3,35 / 2,625,43 / 4,32 / 3,587,17 / 5,67 / 4,72
Water flow (High / Medium / Low)m3/h0,36 / 0,27 / 0,200,59 / 0,49 / 0,380,81 / 0,60 / 0,470,93 / 0,78 / 0,631,29 / 0,99 / 0,84
Water pressure drop (High / Medium / Low)kPa11,13 / 6,7 / 3,823,2 / 16,38 / 11,1425,52 / 15,03 / 9,9518,54 / 13,01 / 8,7130,94 / 18,96 / 14,04
Heating45ºCCapacity (High / Medium / Low) (*2)kW2,39 / 1,76 / 1,33,62 / 2,82 / 2,174,66 / 3,38 / 2,576,38 / 4,81 / 3,938,45 / 6,32 / 5,05
Water flow (High / Medium / Low)m3/h0,42 / 0,32 / 0,240,64 / 0,51 / 0,390,83 / 0,60 / 0,471,10 / 0,87 / 0,711,47 / 1,13 / 0,90
Water pressure drop (High / Medium / Low)kPa8,9 / 7,29 / 4,319,57 / 15,1 / 9,821,58 / 12,5 / 7,9117,62 / 15,39 / 10,727,39 / 21,6 / 14,12
50ºCCapacity (High / Medium / Low) (*3)kW2,78 / 2,07 / 1,424,37 / 3,34 / 2,635,52 / 3,98 / 3,037,44 / 5,69 / 4,719,96 / 7,48 / 5,94
Water flow (High / Medium / Low)m3/h0,36 / 0,27 / 0,200,59 / 0,49 / 0,380,81 / 0,60 / 0,470,93 / 0,78 / 0,631,29 / 0,99 / 0,84
Water pressure drop (High / Medium / Low)kPa11,99 / 5,22 / 322,9 / 13,86 / 9,123,02 / 12,41 / 7,724,16 / 12,51 / 8,534,9 / 16,71 / 12,38
Air flow rate (High / Medium / Low)m3/h369 / 272 / 196604 / 448 / 343678 / 492 / 3831.017 / 720 / 5881.509 / 1054 / 806
Version SEPa1212121212
Version CEPa00000
Exchanger water volumeL0,1950,2590,3440,4710,471
Power supplyV / F / Hz220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50
ConsumptionW15302636103
Sound pressure (*4)dB(A)39 / 31 / 2244 / 37 / 3140 / 32 / 2542 / 33 / 2851 / 42 / 35
Operation maximum pressureMPa1,61,61,61,61,6
Inlet water maximum temperatureºC6565656565
Water connectionsinch3/4"3/4"3/4"3/4"3/4"
Drain connectionmm1616161616
DimensionsVersion SE (Width x Height x Depth)mm550 x 545 x 212750 x 545 x 212950 x 545 x 2121.250 x 545 x 2121.250 x 545 x 212
Version CE (Width x Height x Depth)mm800 x 592 x 2201.000 x 592 x 2121.200 x 592 x 2201.500 x 592 x 2201.500 x 592 x 220
WeightVersion SEkg1923,5273434
Version CEkg24,434,234,24040

Notes:

(1) Cooling capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet water temperature 7/12°C; Ambient temp. 27°C DB, 19ºC WB.
(2) Heating capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet water temperature 45/40°C; Ambient temperature 20°C.
(3) Heating capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet water temperature 50°C/*; Ambient temperature 20°C.
(4) Sound pressure level measured in semi-anechoic chamber.

– The above design and specifications are subject to change of product improvement without prior notice.