MUCS-W7 Series

Industrial range

MUCSR-H6

Cassette Fan Coil Unit MUCS-W7 Series

Characteristics

  • 2 Pipes Fan Coil Unit Cassette Type
  • Design 360°
  • Models 14 and 16 with compact size
  • Low noise and low-energy consumption DC fan motor
  • Condensate removal pump
  • Fresh air intake function
  • Ducted outlet for exhaust air in adjacent room
  • Remote ON / OFF signal (optional)
  • Wireless remote control included
  • Wall control with “Follow me” function KJR-29B (optional)
  • Centralized controller CCM (optional on models 14/16/20)

     Technical Documentation

Data SheetES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Owner's and installation manua Mods. 14/16ES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Owner's and installation manua Mods. 20/24/36ES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Service manual Mods. 14/16EN 18X18
Service manual Mods. 20/24/36EN 18X18

TECHNICAL SPECIFICATIONS

 

ModelMUCS-14-W7MUCS-16-W7MUCS-20-W7MUCS-24-W7MUCS-36-W7
CodeCL04420CL04421CL04422CL04423CL04424
CoolingCapacity (High / Medium / Low)(*1)kW3,96 / 3,26 / 2,764,2 / 3,48 / 3,016,12 / 5,45 / 4,67,87 / 7,12 / 6,6711,19 / 8,82 / 7,48
Water flow (High / Medium / Low)m3/h0,7 / 0,58 / 0,510,75 / 0,61 / 0,541,10 / 0,96 / 0,811,44 / 1,28 / 1,221,96 / 1,53 / 1,28
Water pressure dropkPa11,48 / 8,2 / 6,5412,32 / 8,62 / 7,421,3 / 21,3 / 12,422,3 / 18,1 / 16,336,6 / 22,7 / 16,4
Heating45ºCCapacity (High / Medium / Low) (*2)kW4,63 / 3,79 / 3,14,95 / 3,99 / 3,266,27 / 6,53 / 5,439,16 / 8,54 / 7,910,07 / 10,08 / 8,68
Water flow (High / Medium / Low)m3/h0,83 / 0,67 / 0,560,87 / 0,70 / 0,581,39 / 1,20 / 1,001,73 / 1,57 / 1,462,35 / 1,86 / 1,59
Water pressure dropkPa9,2 / 8,6 / 69,4 / 8,23 / 6,130 / 22,7 / 16,328,8 / 24 / 20,749,2 / 31,2 / 23,3
50ºCCapacity (High / Medium / Low) (*3)kW5,4 / 4,34 / 3,575,76 / 4,69 / 3,848,62 / 7,49 / 6,2710,92 / 9,84 / 9,1614,92 / 11,73 / 10,07
Water flow (High / Medium / Low)m3/h0,7 / 0,58 / 0,510,75 / 0,61 / 0,541,10 / 0,96 / 0,811,44 / 1,28 / 1,221,96 / 1,53 / 1,28
Water pressure dropkPa12,68 / 6,4 / 4,9211,41 / 6,5 / 5,4119,1 / 14,8 / 10,620 / 16,2 / 14,734,3 / 21,3 / 15
Air flow rate (High / Medium / Low)m3/h719 / 561 / 448781 / 611 / 4941.229 / 1.020 / 8101.581 / 1.371 / 1.2361.871 / 1.415 / 1.198
Exchanger water volumeL0,3060,3060,6771,0151,015
Power supplyV / F / Hz220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50
ConsumptionW27325090124
Sound pressure (High / Medium / Low) (*4)dB(A)42 / 36 / 3043 / 38 / 3244 / 40 / 3448 / 44 / 4149 / 43 / 39
Max. working pressureMPa1,61,61,61,61,6
Fresh air intakemm6565757575
Water connectionsinch3/4"3/4"3/4"3/4"3/4"
Drain connectionmm2525323232
DimensionsBody (Width x Height x Depth)mm575 x 261 x 575575 x 261 x 575840 x 230 x 840840 x 300 x 840840 x 300 x 840
Panel (Width x Height x Depth)mm647 x 50 x 647647 x 50 x 647950 x 45 x 950950 x 45 x 950950 x 45 x 950
Weightkg1919293335,5

Notes:

(1) Cooling capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet water temperature 7/12°C; Room temp. 27°C DB, 19ºC WB

(2) Heating capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet water temperature 45/40°C; Room temp. 20ºC.

(3) Heating capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet water temperature 50°C/*; Room temp. 20ºC.

(4) Sound pressure level measured in semi-anechoic chamber.

– The above design and specifications are subject to change of product improvement without prior notice.