MUCSW-HG Series

Industrial range

Cassette Fan Coil Unit MUCSW-HG Series

Cassette Fan Coil Unit MUCSW-HG Series

Characteristics

  • Extremely silent
  • Impulsion of side air
  • Minimum consumption
  • New design
  • Infrared remote control
  • Centrifugal fan
  • Addressable air flow
  • 2 Tubes
  • Possibility of master/slave connection. Turning on one unit, all units turn on

TECHNICAL SPECIFICATIONS

 

ModelMUCSW-09HGMUCSW-12HGMUCSW-
16HG
MUCSW-
18HG
MUCSW-
21HG
MUCSW-
24HG
MUCSW-
36HG
MUCSW-
42HG
MUCSW-
48HG
MUCSW-
60HG
MUCSW-
64HG
CodeCL04401CL04402CL04403CL04405CL04406CL04407CL04409CL04410CL04411CL04413CL04414
Cooling capacityTotalW230030003800510061007300950011500135001530017100
SensibleW1600210027003600430051006700810095001070012300
Heating capacityW2800320042005300630084001050012600147002300025000
Absorbed powerW3746607690132152189220330408
Air flow ratem3/h4505106808501020136017002040238028903400
Noise level (max.)dB(A)3839424445474951535765
Water flowl/h3965166538771049125516341978232226402720
Battery load lossKpa79111618191719223648
Pipes (in/outlet)inch3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"
Dimensions (L x W x H)mm580x580
x290
580x580
x290
580x580
x290
701x701
x290
701x701
x290
811x811
x290
811x811
x290
811x811
x290
960x960
x290
960x960
x290
960x960
x290
WeightKg24242429,529,5373737595959

* Power supply: 220V-240V/1/50Hz

Nominal Power COOL: Bulb temperature 27 °C. Wet Bulb Temperature: 19,5°C. Water inlet: 7°C. Outlet: 12°C

Nominal power HEAT: Dry bulb temperature: 20°C. Water inlet: 60°C