Industrial Range
In traditional air cooling systems the output capacity is monitored by on / off compressor control. The accuracy of the control mode is not very good and the compressor starts and stops frequently, which is not too good for its useful life.
The Digital Scroll air-cooled system breaks the traditional design. It is designed with a parallel connection of a Digital Scroll compressor and one (or two) fixed Scroll compressors. The system can achieve a linear fit of its capacity, from 0.5 % to 100 %, this range is one of the larger from the sector. When the system is operating at partial load, it is possible to adjust accurately the cooling or heating power.
Modular design that allows up to 16 units can operate together, it can form an equipment of up to 1 024 kW.
Easy connection between the master and slave units. All units can be connected via a wired remote control (included with each unit) using a three pole shielded cable.
If the unit gives an error code (E *)
– If it is in the master unit, all units stop (a slave unit can be configured as master unit to leave the system in service temporarily).
– If the error is in a slave unit, just that unit stops.
If the unit gives a protection code (P *), the unit stops but the rest keep ongoing, regardless of whether it is not the master unit (except PE and P9 codes).
More reliable system thanks to the new heat exchangers. 30 kW modules incorporate a heat exchanger of double pipe, while the 65 kW modules carry shell and tube heat exchanger.
From the display of the electronic board of the unit you can check various operating parameters in real time.
All series units incorporate a control that lets you adjust all operating parameters.
Design optimized to minimize fan noise level.
Model | MUEN-30-HG | MUEN-65-HG | |||
---|---|---|---|---|---|
Code | CL25604 | CL25605 | |||
Power supply | F, V, Hz | 3N-, 400, 50 | 3N-, 400, 50 | ||
Cooling (1) | Capacity | kW | 30 | 65 | |
Power consumption | kW | 10 | 20,4 | ||
Current | A | 16,3 | 36,5 | ||
Max. current | A | 24 | 54,5 | ||
Heating (2) | Capacity | kW | 32 | 69 | |
Power consumption | kW | 9,8 | 21,5 | ||
Current | A | 16 | 37,2 | ||
Max. current | A | 24 | 54,5 | ||
Compressors | Brand | Copeland | Copeland | ||
Type | Scroll | Scroll | |||
Digital Scroll | Model | ZPD67KCE-TFD-532 | ZPD72KCE-TFD-433 | ||
Quantity | 1 | 1 | |||
Capacity | kW | 16,2 | 16,9 | ||
Power consumption | kW | 5,26 | 5,75 | ||
Max. intensity | A | 11,8 | 12,7 | ||
Fixed 1 | Model | ZP67KCE-TFD-522 | ZP144KCE-TFD-522 | ||
Quantity | 1 | 1 | |||
Capacity | kW | 16,2 | 35,4 | ||
Power consumption | kW | 5,2 | 10,8 | ||
Max. intensity | A | 10,6 | 21,1 | ||
Fixed 2 | Model | -- | ZP67KCE-TFD-420 | ||
Quantity | -- | 1 | |||
Capacity | kW | -- | 16,2 | ||
Power consumption | kW | -- | 5,2 | ||
Max. intensity | A | -- | 11,8 | ||
Fan | Quantity | 1 | 2 | ||
Air Flow | m3/h | 12.000 | 24.000 | ||
Power | kW | 0,67 | 0.865 x 2 | ||
Sound pressure (3) | dB | 65 | 67 | ||
Water exchanger | Type | Double tube | Shell and tube | ||
Pressure drop | Kpa | 60 | 15 | ||
Volume | L | 10 | 42 | ||
Nominal flow | m3/h | 5,2 | 11,2 | ||
Max. pressure Design | Mpa | 1 | 1 | ||
Connection type | Flanged | Flanged | |||
Hydraulic connections | mm | DN40 (1 1/2) | DN 100 (4) | ||
Dimensions | Net (W x H x D) | mm | 1514 x 1865 x 841 | 2000 x 1880 x 900 | |
Gross (W x H x D) | mm | 1590 x 2065 x 995 | 2090 x 2020 x 985 | ||
Weight | Net | Kg | 380 | 600 | |
Gross | Kg | 400 | 670 | ||
Refrigerant | Type | R410A | R410A | ||
Quantity | Kg | 7 | 14 | ||
Electrical connections (4) | Power cable | m2 | 4 x 16 + T (L<20m) | 4 x 25 + T (L<20m) | |
Communication cable | m2 | 3 x 0,75 (shielded) | 3 x 0,75 (shielded) | ||
Ambient temperature in operation | Cooling | ºC | 10 to 46 | 10 to 46 | |
Heating | ºC | -10 to 21 | -10 to 21 | ||
Water temperature in operation (5) | Cooling | ºC | 5 to 17 | 5 to 17 | |
Heating | ºC | 40 to 50 | 40 to 50 |
Notes:
(1) Nominal conditions cooling: Water temperature 12 °C (Inlet), 7 °C (Outlet), outside temperature 35 °C DB. Water flow 0.172 m3 / (h · KW).
(2) Nominal conditions heating: Water temperature 40 °C (Inlet), 45 °C (Outlet), outside temperature 7 °C DB and 6 °C WB. Water flow 0.172 m3 / (h · KW).
(3) Measured sound level at 1m distance.
(4) Power wiring recommended for L < 20 m, for longer distances will be calculated.
(5) To 65 kW model, it is possible to adjust the cooling water temperature from 0 to 17 °C and in heating from 22 to 55 °C. (Check the technical manual)