Industrial Range
All range units incorporate a DC Inverter fan motor and a compressor, in this way performance is improved in middle frequencies and ensure a more sensitive and effective control.
With the new water circulating pump in compliance with the Ecodesign Directive ERP, power consumption is reduced.
Hydraulic module is fully integrated and equipped with key hydraulic components such as expansion tank, plate type of heat exchanger and water circulating pump.
The plate-type heat exchanger is made of stainless steel AISI 316 to ensure high efficiency of thermal exchange. It is also equipped with an electrical heater and a pressure differential switch.
Possibility of a ON/OFF function and Mode selection by using a potential free signal.
The MUENR-H6 equipments can operate in extreme temperatures, in heating mode up to an outside temperature of -15 °C and in cooling mode up to 46 °C.
Thanks to the plate heat exchanger and high efficiency compressor and fan Inverter DC motor, power consumption is reduced and the unit operation is optimized.
All range units incorporate a control panel that lets you adjust all operating parameters. It is also possible to get a wall-mounted wire control. This way, you can control the unit from indoors. (KJR-120F1-BMK-E (CL92340))
Model | MUENR-05-H6 | MUENR-07-H6 | MUENR-10-H6 | MUENR-12-H6 | MUENR-12-H6T | MUENR-14-H6T | MUENR-16-H6T | |||
---|---|---|---|---|---|---|---|---|---|---|
Code | CL25620 | CL25621 | CL25622 | CL25623 | CL25626 | CL25627 | CL25628 | |||
Power supply | V / F / Hz | 220 - 240 / 1N / 50 | 220 - 240 / 1N / 50 | 220 - 240 / 1N / 50 | 220 - 240 / 1N / 50 | 380 - 415 / 3N / 50 | 380 - 415 / 3N / 50 | 380 - 415 / 3N / 50 | ||
Cooling | Condiciones 1 *(1) | Capacity (min. - max.) | kW | 5,0 (1,9 ~ 5,8) | 7,0 (2,1 ~ 7,8) | 10,0 (2,9 ~ 10,5) | 11,2 (3,1 ~ 12,0) | 11,2 (3,1 ~ 12,0) | 12,5 (3,3 ~ 14,0) | 14,5 (3,5 ~ 15,5) |
Consumption | kW | 1,55 | 2,25 | 2,95 | 3,50 | 3,38 | 3,90 | 4,70 | ||
EER | kW / kW | 3,23 | 3,11 | 3,39 | 3,20 | 3,31 | 3,20 | 3,10 | ||
Condiciones 2 *(2) | Capacity | kW | 5,60 | 8,00 | 10,60 | 12,20 | 12,20 | 14,20 | 15,60 | |
Consumption | kW | 1,15 | 1,85 | 2,30 | 2,65 | 2,60 | 3,10 | 3,60 | ||
EER | kW / kW | 4,87 | 4,32 | 4,24 | 4,60 | 4,70 | 4,58 | 4,33 | ||
SEER | kW / kW | 5,83 | 6,07 | 5,71 | 6,37 | 6,18 | 6,69 | 6,78 | ||
Heating | Condiciones 3 *(3) | Capacity (min. - max.) | kW | 6,2 (2,1 ~ 7,0) | 8,0 (2,3 ~ 9,0) | 11,0 (3,1 ~ 12,0) | 12,3 (3,3 ~ 13,2) | 12,3 (3,3 ~ 13,2) | 13,8 (3,5 ~ 15,4) | 16,0 (3,7 ~ 17,0) |
Consumption | kW | 1,90 | 2,50 | 3,14 | 3,78 | 3,72 | 4,25 | 4,85 | ||
COP | kW / kW | 3,26 | 3,20 | 3,50 | 3,25 | 3,31 | 3,25 | 3,30 | ||
Condiciones 4 *(4) | Capacity | kW | 6,20 | 8,60 | 11,50 | 13,00 | 13,00 | 15,10 | 16,50 | |
Consumption | kW | 1,35 | 2,10 | 2,65 | 2,92 | 2,85 | 3,35 | 3,92 | ||
COP | kW / kW | 4,60 | 4,10 | 4,34 | 4,45 | 4,56 | 4,51 | 4,21 | ||
SCOP | kW / kW | 3,55 | 3,46 | 3,34 | 3,46 | 3,66 | 3,78 | 3,39 | ||
Energy rating at low temperature (35°C / ηs) | A+ / 138,9% | A+ / 135,3% | A+ / 130,7% | A+ / 135,4% | A+ / 143,5% | A+ / 148,3% | A+ / 132,6% | |||
Max. current | A | 11,40 | 13,70 | 25,00 | 26,00 | 8,90 | 9,6 | 10,1 | ||
Compressor | Model | SNB172FJGMC | SNB172FJGMC | ATQ420D1UMU | ATQ420D1UMU | ATQ420D2UMU | ATQ420D2UMU | ATQ420D2UMU | ||
Brand | Mitsubishi Electric | Mitsubishi Electric | GMCC | GMCC | GMCC | GMCC | GMCC | |||
Refrigerant oil | Type | FV50S | FV50S | VG74 | VG74 | VG74 | VG74 | VG74 | ||
Amount | ml | 400 | 400 | 1.400 | 1.400 | 1.400 | 1.400 | 1.400 | ||
Fan | Air flow rate | AXIAL / DC / 1 | AXIAL / DC / 1 | AXIAL / DC / 2 | AXIAL / DC / 2 | AXIAL / DC / 2 | AXIAL / DC / 2 | AXIAL / DC / 2 | ||
Water flow (min ~ max) | m3/h | 5.100 | 5.100 | 7.000 | 7.000 | 7.000 | 7.000 | 7.000 | ||
Plate-type heat exchanger | Water flow (min ~ max) | m3/h | 0,86 (0,77 ~ 0,95) | 1,24 (1,08 ~ 1,54) | 1,72 (1,54 ~ 1,89) | 1,92 (1,72 ~ 2,11) | 1,92 (1,72 ~ 2,11) | 2,15 (1,93 ~ 2,36) | 2,49 (2,24 ~ 2,73) | |
Water volume | L | 0,53 | 0,53 | 0,7 | 0,78 | 0,78 | 0,78 | 1,06 | ||
Lost of final load | kPa | 15 | 15 | 18 | 18 | 18 | 18 | 19 | ||
Water pump | Model | RS15/6 RKC | RS15/6 RKC | RS25/7,5 RKC | RS25/7,5 RKC | RS25/7,5 RKC | RS25/7,5 RKC | RS25/7,5 RKC | ||
Maximum flow rate | m3/h | 3,3 | 3,3 | 4 | 4 | 4 | 4 | 4 | ||
Height | m | 5,5 | 5,5 | 7,5 | 7,5 | 7,5 | 7,5 | 7,5 | ||
Expansion tank | Water volume | L | 2 | 2 | 3 | 3 | 3 | 3 | 3 | |
Max/min water pressure inlet *(5) | kPa | 150 / 500 | 150 / 500 | 150 / 500 | 150 / 500 | 150 / 500 | 150 / 500 | 150 / 500 | ||
Sound pressure *(6) | dB(A) | 58 | 58 | 59 | 59 | 62 | 62 | 62 | ||
Sound power *(6) | dB(A) | 63 | 66 | 67 | 68 | 68 | 70 | 72 | ||
Dimensions (W x H x D) | mm | 990 x 966 x 354 | 990 x 966 x 354 | 970 x 1327 x 400 | 970 x 1327 x 400 | 970 x 1327 x 400 | 970 x 1327 x 400 | 970 x 1327 x 400 | ||
Weight | kg | 81 | 81 | 110 | 110 | 110 | 111 | 111 | ||
Refrigerant | Type | R410A | R410A | R410A | R410A | R410A | R410A | R410A | ||
Amount | kg | 2,5 | 2,5 | 2,8 | 2,8 | 2,8 | 2,9 | 3,2 | ||
Connection wiring | Power supply | mm2 | 2 x 2,5 + T | 2 x 2,5 + T | 2 x 4 + T | 2 x 4 + T | 4 x 2,5 + T | 4 x 2,5 + T | 4 x 2,5 + T | |
Hydraulic connections | Water inlet/outlet | inch | 1" | 1" | 1 1/4" | 1 1/4" | 1 1/4" | 1 1/4" | 1 1/4" | |
Operating temperature range | Cooling | ºC | - 5 ~ 46 | |||||||
Heating | ºC | - 15 ~ 27 (by under 5ºC antifreeze should be added) | ||||||||
Water outlet temperature range | Cooling | ºC | In delivery 4 ~ 20 *(7) | |||||||
Heating | ºC | In delivery 30 ~ 55 *(8) |
Notes:
(1) Conditions 1: Water inlet/outlet temperature: 12 / 7 ºC, outdoor temperature 35ºC DB.
(2) Conditions 2: Water inlet/outlet temperature: 23 / 18 ºC, outdoor temperature 35ºC DB.
(3) Conditions 3: Water inlet/outlet temperature: 40 / 45 °C, outdoor temperature 7°C DB / 6°C WB / 85% HR.
(4) Conditions 4: Water inlet/outlet temperature: 30 / 35 °C, outdoor temperature 7°C DB / 6°C WB / 85% HR.
(5) Pressure level to which pressure switches are activated.
(6) Measured at 1m distance in open field.
(7) The machine controls the return temperature, so that the minimum setting temperature is 10°C, the 4°C are in delivery.
(8) The machine controls the return temperature, so that the maximum setting temperature is 50°C, the 55°C are in delivery.