MUP-W7 Series

Industrial range

CL04315_318

Wall mounted fan coil unit MUP-W7 Series

Characteristics

  • 2 Pipes Fan Coil Unit Wall Type
  • 3 way valves with bypass included
  • Low noise and low-energy consumption DC fan motor
  • Automatic blade swinging
  • Digital display
  • Remote signal ON / OFF
  • Wireless remote control included
  • Wall control with “Follow me” function KJR-29B (Optional)
  • Centralized controller CCM (Optional)

     Technical documentation

Data SheetES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Owner's and installation manualES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Service manualEN 18X18

THECNICAL SPECIFICATIONS

 

ModelMUP-07-W7MUP-09-W7MUP-12-W7MUP-18-W7
CodeCL04315CL04316CL04317CL04318
CoolingCapacity (High / Medium / Low) (*1)kW2,2 / 2,2 / 1,972,64 / 2,48 / 2,063,08 / 2,90 / 2,664,45 / 3,95 / 3,21
Water flowm3/h0,3780,4540,5300,765
Water pressure dropkPa23,133,64236,3
Heating50ºCCapacity (High / Medium / Low) (*2)kW3,02 / 2,85 / 2,353,69 / 2,92 / 2,494,34 / 3,77 / 3,356,30 / 5,17 / 4,18
Water pressure dropkPa2231,44032,8
70ºCCapacity (High / Medium / Low) (*2)kW4,91 / 4,45 / 3,855,52 / 4,56 / 4,086,69 / 5,88 / 5,499,20 / 8,07 / 6,86
Water pressure dropkPa27,534,441,935,1
Air flow rate (High / Medium / Low)m3/h425 / 410 / 320510 / 427 / 349680 / 550 / 5041.020 / 820 / 670
Exchanger water volumeL0,2200,2200,2200,271
Power supplyV / F / Hz220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50220-240 / 1 / 50
Consumption (High)W10,714,33337,5
Sound pressure (High / Medium / Low) (*4)dB(A)30 / 26 / 2332 / 28 / 2536 / 32 / 2940 / 36 / 31
Max. working pressureMPa1,61,61,61,6
Water connectionsinch3/4"3/4"3/4"3/4"
Drain connectionmm20202020
Dimensions (Width x Height x Depth)mm915 × 210 × 290915 × 210 × 290915 × 210 × 2901070 × 210 × 315
Weightkg12121214,8

Notes:

(1) Cooling capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet temp. 7/12 ºC Room temp. 27 ºC DB, 19 ºC WB.

(2) Heating capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet water temperature 50°C/*; Room temp. 20 ºC.

(3) Heating capacity for each of the three air flow rates and according to the conditions: Water inlet/outlet temp. 70/60ºC Room temp. 20 ºC.

(4) Sound pressure level measured in semi-anechoic chamber.

– The above design and specifications are subject to change of product improvement without prior notice.