TECHNICAL SPECIFICATIONS

 

ModelMUC-12-HP4MUC-16-HP4MUC-25-HP4MUC-31-HP4MUC-43-HP4MUC-54-HP4MUC-68-HP4
CodeCL04571CL04572CL04573CL04574CL04575CL04576CL04577
Nominal air flow rateHm3/h6801.0201.3601.7002.3803.0604.080
Mm3/h5107951.0201.2751.7852.2953.060
Lm3/h3405106808501.1901.5302.010
Total power coolingHkW3,74,97,59,312,815,920,1
MkW3,04,06,17,510,412,916,3
LkW2,22,94,55,67,79,512,1
Sensitive cooling
power
HkW2,63,65,46,69,111,514,6
MkW2,12,94,35,37,39,211,7
LkW1,52,13,23,95,46,88,6
Heating powerHkW5,57,511,313,919,124,230,7
MkW4,45,98,911,015,119,224,3
LkW3,04,26,37,710,613,417,0
Water flow ratem3/h0,6360,8461,3021,6082,2022,7363,456
Water pressure losskPa13,622,910,815,732,1911,1
Max. input powerA0,40,70,91,21,52,23,3
Static pressurePa626281103117132122
Exchanger connections"3/4"3/4"3/4"3/4"3/4"3/4"3/4"
Dimensions(W x D x H)mm500 x 825 x 260500 x 825 x 260550 x 1.000 x 315550 x 1.000 x 315650 x 1.200 x 315620 x 1.400 x 350670 x 1.400 x 400
Noise powerdB(A)44475252606266

Notes:

1. Cooling: air intake 27 °C DB /19.5 °C WB, water inlate 7°C, water outlet 12°C.
2. Heating: air intake 21°C , water inlet 60 °C.