Concealed Floor Standing MVD DC

Industrial range

CL23450_CL23453

Concealed Floor Standing MVD DC

Characteristics

  • DC fan motor
  • Display 4 LED
  • Floor unit without housing
  • Includes wireless remote control

     Technical Documentation

Data SheetES 18X18
Owner's manualES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Installation manualES 18X18EN 18X18
Service manualEN 18X18

TECHNICAL SPECIFICATIONS

 

ModelMVD-22Z/DHN1-F3BMVD-28Z/DHN1-F3BMVD-36Z/DHN1-F3BMVD-45Z/DHN1-F3BMVD-56Z/DHN1-F3BMVD-71Z/DHN1-F3BMVD-80Z/DHN1-F3B
CodeCL23450CL23451CL23452CL23453CL23454CL23455CL23456
Power supplyF, V, Hz1N, 220-240, 50/60
Cooling (1)CapacitykW2,22,83,64,55,67,18
Power consumptionW24242124386262
Heating (2)CapacitykW2,63,24,05,06,389
Power consumptionW23241924416563
FanTypeDC
ModelWZDK100-38GS-2WZDK100-38GS-2WZDK100-38GS-2WZDK100-38GS-2WZDK100-38GS-3WZDK100-38GS-3YSK74-4E
Air flow (High/Medium/Low)m3/h530 / 456 / 400569 / 485 / 421624 / 522 / 375660 / 542 / 4401150 / 970 / 8301380 / 1100 / 8701380 / 1100 / 870
Sound pressure (High/Medium/Low) (3)dB(A)36 / 33 / 2936 / 33 / 2937 / 34 / 3037 / 34 / 3041 / 35 / 3144 / 39 / 3344 / 39 / 33
Indoor unitDimensions (W x H x D)Netmm840 x 545 x 212840 x 545 x 2121040 x 545 x 2121040 x 545 x 2121340 x 545 x 2121340 x 545 x 2121340 x 545 x 212
Grossmm939 x 639 x 305939 x 639 x 3051139 x 639 x 3051139 x 639 x 3051425 x 639 x 3051425 x 639 x 3051425 x 639 x 305
WeightNetKg21212828323235
GrossKg25253333383839
DrainageConnectionmm25
RefrigerantTypeR410A
Design pressureHighMpa4,4
LowMpa2,6
Pipe connectionsLiquidmm (pulg.)6,35 (1/4)6,35 (1/4)6,35 (1/4)6,35 (1/4)9,52 (3/8)9,52 (3/8)9,52 (3/8)
Gasmm (pulg.)12,7 (1/2)12,7 (1/2)12,7 (1/2)12,7 (1/2)15,9 (5/8)15,9 (5/8)15,9 (5/8)
Power connections (4)Powermm22 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)
Remote controlModelRM05
TypeWireless

Notas:

(1) Nominal cooling conditions : Indoor 27 °C DB, 19 °C WB and outdoor 35°C DB, pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7°C DB, pipe length of 8 m and a of height difference of 0 m.

(3) Noise level measured in semi-anechoic chamber at 1m distance front and 1.5m high.

(4) Power wiring recommended for L < 20 m, for longer distances will be calculated.