Console MVD DC

Industrial range

CL23420_CL23423

Console MVD DC

Characteristics

  • DC fan motor
  • Display 4 LED
  • Bottom and top air outlet
  • Include wireless remote control

     Technical Documentation

Data SheetES 18X18
Owner's manualES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Installation manualES 18X18EN 18X18
Service manualEN 18X18

TECHNICAL SPECIFICATIONS

 

ModelMVD-22Z/DHN1-BMVD-28Z/DHN1-BMVD-36Z/DHN1-BMVD-45Z/DHN1-B
CodeCL23420CL23421CL23422CL23423
Power supplyF, V, Hz1N, 220-240, 50
Cooling (1)CapacitykW2,22,83,64,5
Power consumptionW20252545
Heating (2)CapacitykW2,63,24,05,0
Power consumptionW20252545
FanTypeDC
ModelRD-280-20-8ARD-280-20-8ARD-280-20-8ARD-280-20-8A
Air flow (High/Medium/Low)m3/h430 / 345 / 229510 / 430 / 229510 / 430 / 229660 / 512 / 400
Sound pressure (High/Medium/Low) (3)dB(A)38 / 32 / 2639 / 33 / 2739 / 33 / 2742 / 39 / 36
Indoor unitDimensions (W x H x D)Netmm700 x 600 x 210700 x 600 x 210700 x 600 x 210700 x 600 x 210
Grossmm810 x 710 x 305810 x 710 x 305810 x 710 x 305810 x 710 x 305
WeightNetKg14151515
GrossKg19202020
DrainageConnectionmm16
RefrigerantTypeR410A
Design pressureHighMpa4,4
LowMpa2,6
Pipe connectionsLiquidmm (pulg.)6,35 (1/4)6,35 (1/4)6,35 (1/4)6,35 (1/4)
Gasmm (pulg.)12,7 (1/2)12,7 (1/2)12,7 (1/2)12,7 (1/2)
Power connections (4)Powermm22 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)
Remote controlModelRM05
TypeWireless

Notes:

(1) Nominal cooling conditions : Indoor 27 °C DB, 19 °C WB and outdoor 35°C DB, pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7°C DB, pipe length of 8 m and a of height difference of 0 m.

(3) Noise level measured in anechoic chamber at 1m distance front and 1.5m high.

(4) Power wiring recommended for L < 20 m, for longer distances will be calculated.