100% Fresh Air Duct MVD DC

Industrial range

CL23381_CL23383-CL23904_CL23906

100% Fresh Air Duct MVD DC

Features

  • DC fan motor
  • Display 4 LED
  • 100% outside air
  • Static pressure up to 200 Pa
  • Include wired remote control

     Technical Documentation

Data SheetES 18X18
Owner's manualES 18X18EN 18X18FR 18X18DE 18X18PT 18X18
Installation manualEN 18X18
ErP InformationEN 18X18
Service manualEN 18X18

TECHNICAL SPECIFICATIONS

 

ModelMVD-125T1/DHN1-FAMVD-140T1/DHN1-FAMVD-200T1/DHN1-FAMVD-250T1/DHN1-FAMVD-280T1/DHN1-FA
CodeCL23390CL23391CL23392CL23393CL23394
Power supplyF, V, Hz1N, 220-240, 50/60
Cooling (1)CapacitykW12,514,020,025,028
Power consumptionW370370615670670
Heating (2)CapacitykW10,512,018,020,022
Power consumptionW370370615670670
FanTypeDC
Quantity1
ModelWZDK750-38GS-WWZDK750-38GS-WWZDK750-38GS-WWZDK750-38GS-WWZDK750-38GS-W
Air flow (High/Medium/Low)m3/h2440 / 2000 / 14702440 / 2000 / 14703860 / 3430 / 28903860 / 3430 / 28903860 / 3430 / 2890
Sound pressure (High/Medium/Low) (3)dB(A)52 / 50 / 4852 / 50 / 4852 / 51 / 1953 / 52 / 5053 / 52 / 50
Static pressure (min-max)Pa20 (0 – 196)20 (0 – 196)62 (40 – 200)62 (40 – 200)62 (40 – 200)
Indoor unitDimensions (W x H x D)Netmm1300 x 420 x 6901300 x 420 x 6901450 x 505 x 9251450 x 505 x 9251450 x 505 x 925
Grossmm1436 x 450 x 7681436 x 450 x 7681509 x 550 x 9901509 x 550 x 9901509 x 550 x 990
WeightNetKg6363108108108
GrossKg7171120120120
DrainageConnectionmm2525323232
RefrigerantTypeR410A
Design pressureHighMpa4,4
LowMpa2,6
Pipe connectionsLiquidmm (pulg.)9,52 (3/8)9,52 (3/8)9,52 (3/8) x 29,52 (3/8) x 29,52 (3/8) x 2
Gasmm (pulg.)15,9 (5/8)15,9 (5/8)15,9 (5/8) x 215,9 (5/8) x 215,9 (5/8) x 2
Power connections (4)Powermm22 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)
Remote controlModelKJR-29B
TypeWiring (6 m)

Notes:

(1) Nominal cooling conditions : Outdoor 33 °C DB and 24 °C WB pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Outdoor 0 °C DB and -1 °C WB pipe length of 8 m and a of height difference of 0 m.

(3) Noise level measured in semi-anechoic chamber at 1m distance front and 1.4m high.

(4) Power wiring recommended for L < 20 m, for longer distances will be calculated.