Cassette 1 Way MVD D4+

Industrial range

CL23150_153

1 Way Cassette MVD D4+

Characteristics

  • Digital LED Display (models 28 and 36)
  • Display 4 LED (models 45 and 56)
  • Input of outside air
  • Include drain pump
  • Include wireless remote control

     Technical Documentation

Owner's manualESEN
Installation manualEN
Service manualES

TECHNICAL SPECIFICATIONS

 

ModelMVD-D28Q1/N1-DMVD-D36Q1/N1-DMVD-D45Q1/N1-CMVD-D56Q1/N1-C
CodeCL23150CL23151CL23152CL23153
Power supplyF, V, Hz1N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 50
Cooling (1)CapacitykW2,83,64,55,6
Power consumptionW41418085
IntensityA0,250,250,370,39
Heating (2)CapacitykW3,2456,3
Power consumptionW41418085
IntensityA0,250,250,370,39
FanBrandWellingWellingWellingWelling
TypeACACACAC
ModelRPS12NRPS12NYSK-55-4YSK-55-4
Air flow (Super High/High/Medium/Low)m3/h573 / 456 / 315573 / 456 / 315704 / 630 / 503860 / 810 / 702
Noise level (High/Medium/Low) (3)dB(A)39 / 37 / 3440 / 38 / 3441 / 39 / 3542 / 40 / 36
Indoor unitDimensionsNet dimensions (W x H x D)mm1054 x 169 x 4251054 x 169 x 4251147 x 200 x 6401147 x 200 x 640
Gross dimensions (W x H x D)mm1155 x 255 x 4901155 x 255 x 4901380 x 265 x 7751380 x 265 x 775
WeightNETKg131331,531,5
GrossKg16,516,537,237,2
PanelModelMBQ1-02DMBQ1-02DT-MBQ1-03AT-MBQ1-03A
DimensionsNet dimensions (W x H x D)mm1180 x 36.5 x 4651180 x 36.5 x 4651425 x 10 x 7551425 x 10 x 755
Gross dimensions (W x H x D)mm1232 x 107 x 5171232 x 107 x 5171500 x 110 x 8701500 x 110 x 870
WeightNETKg3,53,599
GrossKg5,25,21212
DrainageConnectionmm25252525
Pumping height (4)mm750750750750
RefrigerantTypeR410AR410AR410AR410A
Design pressureHighMpa4,44,44,44,4
LowMpa2,62,62,62,6
Cooling connectionsLiquidmm (")6,35 (1/4”)6,35 (1/4”)6,35 (1/4”)9,52 (3/8”)
Gasmm (")12,7 (1/2”)12,7 (1/2”)12,7 (1/2”)15,9 (5/8”)
Power connections (5)Power:mm22 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)
Remote controlModelRM05RM05RM05RM05
TypeWirelessWirelessWirelessWireless

Notes:

(1) Nominal cooling conditions : Indoor 27 °C DB, 19 °C WB and outdoor 35°C DB, pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7°C DB, pipe length of 8 m and a of height difference of 0 m.

(3) Noise level measured in anechoic chamber at 1m distance front and 1.4m high.

(4) Maximum height from the unit shaft.

(5) Power wiring recommended for L < 20 m, for longer distances will be calculated.