Ceiling Floor MVD D4+

Industrial range

CL23200_207

Ceiling Floor MVD D4+

Characteristics

  • Display 4 LED
  • Input of outside air (models 112 and 140)
  • Wide adjustment of air directions
  • Include wired remote control

 

     Technical Documentation

Owner's manualESEN
Installation manualESEN
Service manualES

TECHNICAL SPECIFICATIONS

 

ModelMVD-D36DL/N1-CMVD-D45DL/N1-CMVD-D56DL/N1-CMVD-D71DL/N1-C
CodeCL23200CL23201CL23202CL23203
Power supplyF, V, Hz1N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 50
Cooling (1)CapacitykW3,64,55,67,1
Power consumptionW49120122125
IntensityA0,230,670,670,67
HeatingCapacitykW456,38
Power consumptionW49120122125
IntensityA0,230,670,670,67
FanBrandWellingWellingWellingWelling
TypeACACACAC
ModelYSK25-6LYSK55-4LYSK55-4LYSK55-4L
Flow (High/Medium/Low)m3/h650 / 570 / 500800 / 600 / 500800 / 600 / 500800 / 600 / 500
Noise level (High/Medium/Low) (3)dB(A)40 / 38 / 3643 / 41 / 3843 / 41 / 3843 / 41 / 38
PowerW33,4125125125
Indoor unitDimensionsNet dimensions (W x H x D)mm990 x 203 x 660990 x 203 x 660990 x 203 x 660990 x 203 x 660
Gross dimensions (W x H x D)mm1089 x 296 x 7441089 x 296 x 7441089 x 296 x 7441089 x 296 x 744
WeightNETKg26282828
GrossKg32343434
DrainageConnectionmm16161616
RefrigerantTypeR410AR410AR410AR410A
Design pressureHighMpa4,44,44,44,4
LowMpa2,62,62,62,6
Cooling connectionsLiquidmm (")6,35 (1/4”)6,35 (1/4”)9,52 (3/8”)9,52 (3/8”)
Gasmm (")12,7 (1/2”)12,7 (1/2”)15,9 (5/8”)15,9 (5/8”)
Power connections (4)Powermm22 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)
Remote controlModelRM05RM05RM05RM05
TypeWirelessWirelessWirelessWireless

ModelMVD-D80DL/N1-CMVD-D90DL/N1-CMVD-D112DL/N1-CMVD-D140DL/N1-C
CodeCL23204CL23205CL23206CL23207
Power supplyF, V, Hz1N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 50
Cooling (1)CapacitykW8911,214
Power consumptionW130130182182
IntensityA0,830,831,111,11
HeatingCapacitykW91012,515
Power consumptionW130130182182
IntensityA0,830,831,111,11
FanBrandWellingWellingWellingWelling
TypeACACACAC
ModelYSK80-4AYSK80-4AYSK59-4D x 2YSK59-4D x 2
Flow (High/Medium/Low)m3/h1200 / 900 / 7001200 / 900 / 7001980 / 1860 / 17301980 / 1860 / 1730
Noise level (High/Medium/Low) (3)dB(A)45 / 43 / 4045 / 43 / 4047 / 45 / 4247 / 45 / 42
Power:W14314389.5 x 289.5 x 2
Indoor unitDimensionsNet dimensions (W x H x D)mm1280 x 203 x 6601280 x 203 x 6601670 x 244 x 6801670 x 244 x 680
Gross dimensions (W x H x D)mm1379 x 296 x 7441379 x 296 x 7441764 x 329 x 7601764 x 329 x 760
WeightNETKg34,534,55457,5
GrossKg41415963
DrainageConnectionmm16161616
RefrigerantTypeR410AR410AR410AR410A
Design pressureHighMpa4,44,44,44,4
LowMpa2,62,62,62,6
Cooling connectionsLiquidmm (")9,52 (3/8”)9,52 (3/8”)9,52 (3/8”)9,52 (3/8”)
Gasmm (")15,9 (5/8”)15,9 (5/8”)15,9 (5/8”)15,9 (5/8”)
Power connections (4)Power:mm22 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)
Remote controlModelRM05RM05RM05RM05
TypeWirelessWirelessWirelessWireless

Notes:

(1) Nominal cooling conditions : Indoor 27 °C DB, 19 °C WB and outdoor 35°C DB, pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7°C DB, pipe length of 8 m and a of height difference of 0 m.

(3) Noise level measured in anechoic chamber at 1m distance front and 1.5m high.

(4) Power wiring recommended for L < 20 m, for longer distances will be calculated.