Concealed Floor Standing MVD D4+

Industrial range

CL23250_256

Concealed Floor Standing MVD D4+

Characteristics

  • Display 4 LED
  • Floor unit without housing
  • Includes wireless remote control

     Technical Documentation

Owner's manualESEN
Installation manualEN
Service manualES

TECHNICAL SPECIFICATIONS

 

ModelMVD-D22Z/N1-F3BMVD-D28Z/N1-F3BMVD-D36Z/N1-F3BMVD-D45Z/N1-F3BMVD-D56Z/N1-F3BMVD-D71Z/N1-F3BMVD-D80Z/N1-F3B
CodeCL23250CL23251CL23252CL23253CL23254CL23255CL23256
Power supplyF, V, Hz1N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 50
Cooling (1)CapacitykW2,22,83,64,55,67,18
Power consumptionW4046554988130130
IntensityA0,180,210,220,220,40,560,56
HeatingCapacitykW2,63,2456,389
Power consumptionW4046464988130130
IntensityA0,180,210,220,220,40,560,56
FanBrandWellingWellingYonganYonganWellingYonganYongan
TypeACACACACACACAC
ModelYSK20-4AYSK20-4AYSK20-6YSK20-6YSK28-4EYSK74-4EYSK74-4E
Flow (High/Medium/Low)m3/h530 / 465 / 400569 / 485 / 421624 / 522 / 375660 / 542 / 4401150 / 970 / 8301380 / 1100 / 8701380 / 1100 / 870
Noise level (High/Medium/Low) (3)dB(A)36 / 33 / 2936 / 33 / 2937 / 34 / 3037 / 34 / 3041 / 35 / 3144 / 39 / 3344 / 39 / 33
Static pressurePa12121212121212
Consumption4242494995138,5138,5
Indoor unitDimensionsNet dimensions (W x H x D)mm840 x 544 x 212840 x 544 x 2121036 x 544 x 2121036 x 544 x 2121336 x 544 x 2121336 x 544 x 2121336 x 544 x 212
Gross dimensions (W x H x D)mm939 x 639 x 305939 x 639 x 3051139 x 639 x 3051139 x 639 x 3051439 x 639 x 3051439 x 639 x 3051439 x 639 x 305
WeightNETKg252529,529,5333336
GrossKg27273434393940
DrainageConnectionmm16161616161616
RefrigerantTypeR410AR410AR410AR410AR410AR410AR410A
Design pressureHighMpa4,44,44,44,44,44,44,4
LowMpa2,62,62,62,62,62,62,6
Cooling connectionsLiquidmm (")6,35 (1/4”)6,35 (1/4”)6,35 (1/4”)6,35 (1/4”)9,52 (3/8”)9,52 (3/8”)9,52 (3/8”)
Gasmm (")12,7 (1/2”)12,7 (1/2”)12,7 (1/2”)12,7 (1/2”)15,9 (5/8”)15,9 (5/8”)15,9 (5/8”)
Power connections (4)Power:mm22 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)
Remote controlModelRM05RM05RM05RM05RM05RM05RM05
TypeWirelessWirelessWirelessWirelessWirelessWirelessWireless

Notes:

(1) Nominal cooling conditions : Indoor 27 °C DB, 19 °C WB and outdoor 35°C DB, pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7°C DB, pipe length of 8 m and a of height difference of 0 m.

(3) Noise level measured in anechoic chamber at 1m distance front and 1.5m high.

(4) Power wiring recommended for L < 20 m, for longer distances will be calculated.