Low Silhouette Duct MVD D4+

Industrial range

CL23170_179

Low Silhouette Duct MVD D4+

Characteristics

  • Digital LED Display (models 28 and 140)
  • Display 4 LED (models 45 and 56)
  • Input of outside air
  • Include drain pump
  • Remote ON/OFF signal and alarm
  • Include wired remote control

     Technical Documentation

Owner's manualESEN
Installation manualESEN
Service manualES

TECHNICAL SPECIFICATIONS

 

ModelMVD-D22T2/N1-B5MVD-D28T2/N1-B5MVD-D36T2/N1-B5MVD-D45T2/N1-B5MVD-D56T2/N1-B5
CodeCL23170CL23171CL23172CL23173CL23174
Power supplyF, V, Hz1N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 50
Cooling (1)CapacitykW2,22,83,64,55,6
Power consumptionW626267115115
IntensityA0,310,310,340,580,58
Heating (2)CapacitykW2,63,2456,3
Power consumptionW626267115115
IntensityA0,310,310,340,580,58
FanBrandWellingWellingWellingWellingWelling
TypeACACACACAC
ModelYSK27-4CYSK27-4CYSK27-4CYSK68-4PYSK68-4P
Air flow (Super High/High/Medium/Low)m3/h570 / 530 / 410 / 320570 / 530 / 410 / 320570 / 530 / 410 / 320958 / 850 / 667 / 583958 / 850 / 667 / 583
Sound pressure (High/Medium/Low) (3)dB(A)38 / 35 / 3238 / 35 / 3240 / 38 / 3641 / 38,9 / 3641 / 38,9 / 36
Static pressurePa10 (10-30)10 (10-30)10 (10-30)10 (10-30)10 (10-30)
Power:W626267107107
Indoor unitDimensionsNet dimensions (W x H x D)mm700 x 210 x 635700 x 210 x 635700 x 210 x 635920 x 210 x 635920 x 210 x 635
Gross dimensions (W x H x D)mm915 x 290 x 655915 x 290 x 655915 x 290 x 6551135 x 290 x 6551135 x 290 x 655
WeightNETKg21,521,5222727
GrossKg262626,53232
Outside air inlet diametermm125125125125125
DrainageConnectionmm3232323232
Pumping height (4)mm750750750750750
RefrigerantTypeR410AR410AR410AR410AR410A
Design pressureHighMpa4,44,44,44,44,4
LowMpa2,62,62,62,62,6
Cooling connectionsLiquidmm (")6,35 (1/4”)6,35 (1/4”)6,35 (1/4”)6,35 (1/4”)9,52 (3/8”)
Gasmm (")12,7 (1/2”)12,7 (1/2”)12,7 (1/2”)12,7 (1/2”)15,9 (5/8”)
Power connections (5)Powermm22 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)
Remote controlModelKJR-29BKJR-29BKJR-29BKJR-29BKJR-29B
TypeWiringWiringWiringWiringWiring

ModelMVD-D71T2/N1-B5MVD-D80T2/N1-B5MVD-D90T2/N1-B5MVD-D112T2/N1-B5MVD-D140T2/N1-B5
CodeCL23175CL23176CL23177CL23178CL23179
Power supplyF, V, Hz1N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 501N-, 220-240, 50
Cooling (1)CapacitykW7,18911,214
Power consumptionW163231231327357
IntensityA0,821,161,161,651,8
Heating (2)CapacitykW891012,515,5
Power consumptionW163231231327357
IntensityA0,821,161,161,651,8
FanBrandWellingWellingWellingWellingWelling
TypeACACACACAC
ModelYSK74-4PYSK100-4PYSK100-4PYSK200-4PYSK180-4P
Air flow (Super High/High/Medium/Low)m3/h1207 / 1050 / 905 / 8211558 / 1350 / 1167 / 10331558 / 1350 / 1167 / 10332036 / 1800 / 1564 / 14002138 / 1900 / 1643 / 1405
Sound pressure (High/Medium/Low) (3)dB(A)43,4 / 40 / 3645,4 / 39,8 / 3745,4 / 39,8 / 3748 / 41,9 / 3848 / 43,2 / 39
Static pressurePa10 (10-30)20 (10-50)20 (10-50)40 (10-80)40 (10-100)
PowerW163227227393355
Indoor unitDimensionsNet dimensions (W x H x D)mm1140 x 210 x 6351140 x 270 x 7751140 x 270 x 7751140 x 270 x 7751200 x 300 x 865
Gross dimensions (W x H x D)mm1355 x 290 x 6551355 x 350 x 7951355 x 350 x 7951355 x 350 x 7951400 x 375 x 920
WeightNETKg3140424250
GrossKg3648,5505059,5
Outside air inlet diametermm125125125125125
DrainageConnectionmm3232323232
Pumping height (4)mm750750750750750
RefrigerantTypeR410AR410AR410AR410AR410A
Design pressureHighMpa4,44,44,44,44,4
LowMpa2,62,62,62,62,6
Cooling connectionsLiquidmm (")9,52 (3/8”)9,52 (3/8”)9,52 (3/8”)9,52 (3/8”)9,52 (3/8”)
Gasmm (")15,9 (5/8”)15,9 (5/8”)15,9 (5/8”)15,9 (5/8”)15,9 (5/8”)
Power connections (5)Power:mm22 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)2 x 2,5 + T (L<20m)
Comunication cablemm23 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)3 x 0,75 (shielded)
Remote controlModelKJR-29BKJR-29BKJR-29BKJR-29BKJR-29B
TypeWiringWiringWiringWiringWiring

Notes:

(1) Nominal cooling conditions : Indoor 27 °C DB, 19 °C WB and outdoor 35°C DB, pipe length of 8 m and a height difference of 0 m.

(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7°C DB, pipe length of 8 m and a of height difference of 0 m.

(3) Noise level measured in anechoic chamber at 1m distance front and 1.4m high.

(4) Maximum height from the unit shaft.

(5) Power wiring recommended for L < 20 m, for longer distances will be calculated.