Industrial Range
The modular system Super DC Inverter Maxi MVD V5X (2 pipes) consists of 8 basic modules that can be combined, allowing a maximum power of 246 kW and being the highest and a maximum pipe length up to 1000 m.
Model | MVD-V5X252W/V2GN1 | MVD-V5X280W/V2GN1 | MVD-V5X335W/V2GN1 | MVD-V5X400W/V2GN1 | |||
---|---|---|---|---|---|---|---|
Code | CL23300 | CL23301 | CL23302 | CL23303 | |||
Power supply | F, V, Hz | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | ||
Cooling (1) | Capacity | kW | 25,2 | 28 | 33,5 | 40 | |
Consumption (7) | kW | 6,25 | 7,49 | 8,91 | 11,66 | ||
EER (7) | 4,03 | 3,74 | 3,76 | 3,43 | |||
Heating (2) | Capacity | kW | 27 | 31,5 | 37,5 | 45 | |
Consumption (7) | kW | 5,3 | 6,89 | 8,91 | 9,83 | ||
COP (7) | 5,09 | 4,57 | 4,21 | 4,07 | |||
Current | A | 20,0 | 21,0 | 23,0 | 27,3 | ||
Connectivity | Connectable capacity | % | 50 - 130 | 50 - 130 | 50 - 130 | 50 - 130 | |
Max. number of interiors | 13 | 16 | 20 | 23 | |||
Compressor | Brand | Hitachi | Hitachi | Hitachi | Hitachi | ||
Type | DC Inverter | DC Inverter | DC Inverter | DC Inverter | |||
Quantity | 1 | 1 | 1 | 2 | |||
Model No. 1 | E655DHD-65D2YG | E655DHD-65D2YG | E705DHD-72D2YG | E405DHD-42D2YG | |||
Model No. 2 | -- | -- | -- | E405DHD-42D2YG | |||
Fan | Type | DC | DC | DC | DC | ||
Quantity | 1 | 1 | 1 | 2 | |||
Flow rate | m3/h | 12.000 | 12.000 | 12.000 | 14.000 | ||
Static pressure | Standard | Pa | 0 - 20 | 0 - 20 | 0 - 20 | 0 - 20 | |
Adjustable | Pa | 20 - 40 | 20 - 40 | 20 - 40 | 20 - 40 | ||
Sound pressure *** | dB(A) | 58 | 59 | 60 | 62 | ||
Dimensions | Net dimensions (W x H x D) | mm | 990 x 1635 x 790 | 990 x 1635 x 790 | 990 x 1635 x 790 | 1340 x 1635 x 790 | |
Net dimensions (W x H x D) | mm | 1055 x 1805 x 855 | 1055 x 1805 x 855 | 1055 x 1805 x 855 | 1405 x 1805 x 855 | ||
Weight | NET | Kg | 219 | 219 | 237 | 297 | |
Gross | Kg | 234 | 234 | 252 | 315 | ||
Refrigerant | Type / GWP | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | ||
Quantity | Kg | 9 / 18,79 | 9 / 18,79 | 11 / 22,97 | 13 / 27,14 | ||
Pipe length (4) | Max. Heigh | ODU Upper | m | 90 | 90 | 90 | 90 |
ODU Lower | m | 110 | 110 | 110 | 110 | ||
Total | m | 1.000 | 1.000 | 1.000 | 1.000 | ||
Pipe connections (5) | Liquid | mm | 12,7 (1/2) | 12,7 (1/2) | 15.9 (5/8") | 15.9 (5/8") | |
Gas | mm | 25,4 (1") | 25,4 (1") | 28,6 (1 1/8) | 31,8 (1 1/4") | ||
Oil balance | mm | 6,35 (1/4") | 6,35 (1/4") | 6,35 (1/4") | 6,35 (1/4") | ||
Power connections (6) | Power / Fuse | mm2 / A | 4 x 6 + T / 25 | 4 x 6 + T / 25 | 4 x 6 + T / 25 | 4 x 10 + T / 30 | |
Comunication cable | mm2 | 3 x 0,75 (shielded) | 3 x 0,75 (shielded) | 3 x 0,75 (shielded) | 3 x 0,75 (shielded) | ||
Working temperature range | Cooling | ºC | -5 to 43 | -5 to 43 | -5 to 43 | -5 to 43 | |
Heating | ºC | -20 to 24 | -20 to 24 | -20 to 24 | -20 to 24 |
Model | MVD-V5X450W/V2GN1 | MVD-V5X500W/V2GN1 | MVD-V5X560W/V2GN1 | MVD-V5X615W/V2GN1 | |||
---|---|---|---|---|---|---|---|
Code | CL23304 | CL23305 | CL23306 | CL23307 | |||
Power supply | F, V, Hz | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | 3N-, 400, 50/60 | ||
Cooling (1) | Capacity | kW | 45 | 50 | 56 | 61,5 | |
Consumption (7) | kW | 10,98 | 12,82 | 14,51 | 16,44 | ||
EER (7) | 4,10 / 7,20 | 3,90 / 7,36 | 3,86 / 7,28 | 3,74 / 7,04 | |||
Heating (2) | Capacity | kW | 50 | 56 | 63 | 69 | |
Consumption (7) | kW | 10,87 | 13,18 | 15,29 | 17,12 | ||
COP (7) | 4,60 / 5,82 | 4,25 / 5,67 | 4,12 / 5,50 | 4,03 / 5,25 | |||
Current | A | 29,9 | 34,4 | 41,2 | 44,9 | ||
Connectivity | Connectable capacity | % | 50 - 130 | 50 - 130 | 50 - 130 | 50 - 130 | |
Max. number of interiors | 26 | 29 | 33 | 36 | |||
Compressor | Brand | Hitachi | Hitachi | Hitachi | Hitachi | ||
Type | DC Inverter | DC Inverter | DC Inverter | DC Inverter | |||
Quantity | 2 | 2 | 2 | 2 | |||
Model No. 2 | Model | E405DHD-42D2YG | E405DHD-36D2YG | E705DHD-72D2YG | E705DHD-72D2YG | ||
Model No. 2 | E405DHD-42D2YG | E705DHD-72D2YG | E705DHD-72D2YG | E705DHD-72D2YG | |||
Fan | Type | DC | DC | DC | DC | ||
Quantity | 2 | 2 | 2 | 2 | |||
Flow rate | m3/h | 14.000 | 16.000 | 16.000 | 16.000 | ||
Static pressure | Standard | Pa | 0 - 20 | 0 - 20 | 0 - 20 | 0 - 20 | |
Adjustable | Pa | 20 - 40 | 20 - 40 | 20 - 40 | 20 - 40 | ||
Sound pressure (3) | dB(A) | 62 | 63 | 63 | 63 | ||
Dimensions | Net dimensions (W x H x D) | mm | 1340 x 1635 x 790 | 1340 x 1635 x 790 | 1340 x 1635 x 790 | 1340 x 1635 x 790 | |
Net dimensions (W x H x D) | mm | 1405 x 1805 x 855 | 1405 x 1805 x 855 | 1405 x 1805 x 855 | 1405 x 1805 x 855 | ||
Weight | NET | Kg | 297 | 305 | 340 | 340 | |
Gross | Kg | 315 | 323 | 358 | 358 | ||
Refrigerant | Type / GWP | R410A / 2088 | R410A / 2088 | R410A / 2088 | R410A / 2088 | ||
Quantity | Kg | 13 / 27,14 | 13 / 27,14 | 16 / 33,41 | 16 / 33,41 | ||
Pipe length (4) | Max. Heigh | ODU Upper | m | 90 | 90 | 90 | 90 |
ODU Lower | m | 110 | 110 | 110 | 110 | ||
Total | m | 1.000 | 1.000 | 1.000 | 1.000 | ||
Pipe connections (5) | Liquid | mm | 15.9 (5/8") | 19.1 (3/4") | 19.1 (3/4") | 19.1 (3/4") | |
Gas | mm | 31,8 (1 1/4") | 31,8 (1 1/4") | 31,8 (1 1/4") | 31,8 (1 1/4") | ||
Oil balance | mm | 6,35 (1/4") | 6,35 (1/4") | 6,35 (1/4") | 6,35 (1/4") | ||
Power connections (6) | Power / Fuse | mm2 / A | 4 x 10 + T / 35 | 4 x 16 + T / 40 | 4 x 16 + T / 50 | 4 x 16 + T / 50 | |
Comunication cable | mm2 | 3 x 0,75 (shielded) | 3 x 0,75 (shielded) | 3 x 0,75 (shielded) | 3 x 0,75 (shielded) | ||
Working temperature range | Cooling | ºC | -5 to 43 | -5 to 43 | -5 to 43 | -5 to 43 | |
Heating | ºC | -20 to 24 | -20 to 24 | -20 to 24 | -20 to 24 |
Notes:
(1) Nominal cooling conditions : Indoor 27 °C DB, 19 °C WB and outdoor 35 °C DB, 24ºC WB pipe length of 7.5 m and a height difference of 0 m.
(2) Nominal heating conditions: Indoor 20 °C DB, 15 °C WB and outdoor 7 °C DB, 6ºC WB pipe length of 7.5 m and a of height difference of 0 m.
(3) Noise level measured in semi-anechoic chamber at 1m distance front and 1.3m high.
(4) In case of a height difference higher than 20 m it is recommended to install a oil tramp every 10 m in the gas pipes.
(5) Pipe diameter are of stop valves, this does not mean that the pipe should be this diameter. The oil balance pipe is only needed when two or more modules are connected.
(6) Power wiring recommended for L < 20 m, for longer distances will be calculated.
(7) Data measured under EUROVENT EN 14825 conditions, at 100% simultaneity with indoor units of the duct type.